The incinerators to be supplied shall meet the following specifications
- ISO certified
- Model: 250LA ,multiple diesel fuel combustion chambers
- Performance capacity
- 120Kg/hr GRE 1.25 for HCRW
- 96Kg/hr GRE 1.25 for general waste.
- 40Kg/hr GRE 3.00 for plastic
- Waste type : health care risk waste and general waste
- Chimney stack:
- Chimney : 3.5mm mild steel
- Height from base :11m and if there are buildings within
30m of the incinerator, chimney must extend at least 3m
above the apexes of all the roof of such buildings
- Diameter of chimney at top :430mm
- Weight of stack: ±500 Kg
- Case and stack be painted with 400⁰C heat resistant Black paint
- Burners:
- 1st chamber 850⁰C – 900⁰C
- 2nd chamber 1000⁰C
- Variable speed combustion air blowers
- Primary chamber volume ±1.05 cubic metres
- Mixing chamber volume ±0.30 cubic metres
- Settling chamber volume ±0.89 cubic metres
- Weight excluding chimney ±6.400Kg at manufacture
- .Firing tools supplied :Hoe ,poker and rake
- Dimensions
- Length ±2125mm
- Width ±1890mm
- Height ±2125mm
- Extra width for burners ± 1000mm
- Loading door opening 610 *540mm
- Hearth area ±1.19square metres
- Description of grate/hearth :A full hearth to be supplied to prevent contaminated
- Liquids from flowing into ash pit without being incinerated
- Compliance with South African Atmospheric Pollution Prevention Act No.45 of
1965 or equivalent air pollution standards
- Documents to be supplied :Operations and maintenance manual and standard
operating procedures (SOPs)
- Emission controls:
- heated refractory screen
- Low velocity grit settling chamber
- Stainless steel arrester screen
- Refractory material :alumina content> 49% and thickness average 102mm
- Bake out : to be done over 2-3 days
- Materials of constructions
- Case :5mm mild steel
- Bracing: heavy angle and channel
- Hearth: 1550 ⁰C
- Ashing door: high grade cast iron
- Loading door 5mm mild steel lined with 1550 ⁰C castable general purpose high strength, high abrasion resistant monolithic refractory concrete.
- Incinerator walls and roof: 1550 ⁰C castable monolithic refractory
- Temperature: ≥ 90 ⁰C
- Insulation to walls: 1000 ⁰C castable insulation
- Electricity supply required: 220volt, 15amp single phase
- Controls:
- Draught control: barometer indicator, door operated draught limiter
- Air supply: built-in forced heated air ducts, primary and secondary (intensifier)
- Electric: control panel includes-circuit breakers, main switch, timer, pilot lights, 2 set point pyrometer and one set point pyrometer
Summary of Key Expected Activities/Outputs
- Replacement of pipes from the tank to the incinerator
- Covering pipes to protect them bursting in winter
- Replacement of gauge
- Incinerator installation
- Installation report
- End of contract report